Internal Data Search by Company/Division Name

Data Search on:

The titles below have an association with your requested company name

Corrosion Studies on GeoBrom® HG520 Partial Immersion Study

Brominated derivative products for mercury control… There was little to no corrosion observed on these coupons in the vapor space. Visually, all corrosion occurred in the liquid phase where half of the coupons were suspended. There was no increase in corrosion rate observed at vapor / liquid interface on any of the specimens. Based on this 90 day study, all specimens were less than 0.70 mpy corrosion rate with half the coupon below surface. Mild carbon steel (C-1018) gave the highest corrosion rate at 0.14 mpy at 20° C and 0.65 mpy at 50° C. All remaining specimens were under 0.10 mpy. ICP analysis of GeoBrom® HG520 samples refl ect elevated iron and chromium levels at end of the 90-day period. The maximum allowable corrosion rate for each specimen with GeoBrom® HG520 depends on the application.

Revision Date:  7/20/2015

Tags:  221112 - Fossil Fuel 化石燃料, Great Lakes Solutions, Chemtura, Bromine, Corrosion, Chemicals, Mercury, Mercury Removal, Corrosion


Corrosion Studies on GeoBrom® HG520 Total Immersion Study

A 90-day, total-immersion corrosion rate study was conducted using GeoBrom® HG520 calcium bromide solution and six selected metals at 20° and 50° C. ASTM Method “Standard Practice for Preparing, Cleaning, and Evaluating Corrosion Test Specimens” G1 - 03 (reapproved 2011) was used to prepare, clean, and evaluate tests specimens.

Revision Date:  7/20/2015

Tags:  221112 - Fossil Fuel 化石燃料, Great Lakes Solutions, Chemtura, Chemical, Mercury, Bromine, Mercury Removal, Corrosion


Corrosion Studies on GeoBrom® HG520 Vapor Space Study

A 90-day vapor space corrosion rate study was conducted using GeoBrom® HG520 calcium bromide solution and six selected metals at 20° and 50° C. ASTM Method “Standard Practice for Preparing, Cleaning, and Evaluating Corrosion Test Specimens” G1 - 03 (reapproved 2011) was used to prepare, clean, and evaluate tests specimens.

Revision Date:  7/20/2015

Tags:  221112 - Fossil Fuel 化石燃料, Chemtura, Great Lakes Solutions, Mercury, Chemical, Bromine, Mercury Removal, Corrosion


Calcium Bromide Liquid: Safety and Handling Guide GeoBrom® HG520

Calcium Bromide Liquid: Safety and Handling Guide

Revision Date:  7/20/2015

Tags:  221112 - Fossil Fuel 化石燃料, Great Lakes Solutions, Chemtura, Chemical, Mercury, Bromine, Safety, Mercury Removal, Corrosion