Internal Data Search by Company/Division Name
FGD Wastewater Treatment Webinar - Hot Topic Hour June 16, 2011
Speakers discussed their experience with developing, testing, designing and troubleshooting treatment technologies for FGD wastewater.
Revision Date: 6/16/2011
Tags: 221112 - Fossil Fuel 化石燃料, Brooks Rand Labs, GE Power & Water, Veolia Water Solutions & Technologies, Evonik Degussa GmbH, Infilco Degremont, Wastewater Treatment Chemical, Testing, Mercury, Toxic Metal, Wastewater Treatment
Ruediger Peldszus, Senior Manager for Applied Technology Advanced Intermediates at Evonik Degussa GmbH, backed up his claim that TMT 15® is a good choice for separating heavy metals from flue gas scrubber water by citing a large number of installations in coal-fired power plants and also waste incineration plants. When asked how the chemical impacted the gypsum quality, Ruediger explained that the resultant compound is very small and exits the top of the hydroclone and not with the gypsum through the bottom. TMT 15 can also prevent mercury re-emission from the scrubber but for this to be successful, the parameters must be carefully evaluated. One of the participants has a client who has been challenged to successfully use the TMT 15 to prevent re-emission
Revision Date: 6/16/2011
Tags: 221112 - Fossil Fuel 化石燃料, Evonik Degussa GmbH, Wastewater Treatment Chemical, Mercury, Toxic Metal, Wastewater Treatment